Solar DC String Cable Sizing & Voltage Drop Calculator

Size PV string cable for voltage drop and rooftop temperature derating to AS/NZS 5033.

Last reviewed by the myCalculator Editorial Team

Input Parameters

A
V
m

Measure array to inverter one way; the calculator doubles it for the return path.

%

AS/NZS 5033 recommends keeping DC string voltage drop at or below 3%; 1% to 1.5% is good practice.

°C

Calculation Results

Recommended Cable Size (DC)
4 mm2
Actual Voltage Drop
4.43 V (1.11%)
Design Current (1.25 x Isc)
13.1 A
Temp De-rated Current Required
22.6 A (at 70C)
Allowable Voltage Drop
6 V (1.5% of 400V)
Calculated Min Cable Size
2.95 mm2 (rounded up to 4 mm2)
I2R Power Loss in Cable
58.1 W
Cable DC Resistance
0.3375 ohm (round-trip)
Summary: For 10.5A Isc strings at 400V Voc with 30m one-way run: use 4 mm2 DC solar cable. Actual voltage drop: 4.43V (1.11%) - within the 1.5% AS 4777 limit.
Step-by-Step Calculation Solution
1.Design Current = 1.25 x Isc = 1.25 x 10.5 A = 13.1 A (AS 4777 safety factor)
2.Temperature de-rating at 70C: factor = 0.58 -> Required capacity = 22.6 A
3.Allowable Vdrop = 400V x 1.5% = 6 V
4.Min Cable Area = (2 x L x I x rho) / Vdrop = (2 x 30 x 13.1 x 0.0225) / 6 = 2.95 mm2
5.Selected Standard Size: 4 mm2 (next standard size up)
6.Actual Vdrop = (2 x 30 x 13.1 x 0.0225) / 4 = 4.43 V (1.11%)
7.I2R loss = 13.1^2 x 0.3375 ohm = 58.1 W

Formula & How Solar DC String Cable Sizing & Voltage Drop Calculator Works

Mathematical Formula
Vdrop = 2 × L × I × ρ / A | A_min = 2 × L × I × ρ / (Vdrop_allowable)

DC string cable is sized for voltage drop rather than thermal capacity, because a long roof run at low current can still lose significant energy. The drop is calculated over twice the one-way length to account for the return conductor. Rooftop cable also runs far hotter than the 30 °C reference ambient — surfaces regularly reach 70 °C in an Australian summer — so the conductor's current rating must be derated before checking compliance. Worked example: with a short-circuit current of 10.5 A, a 30 m one-way run and an allowable drop of 1.5% of 400 V (6 V), copper at roof temperature of 70°C has a resistivity of about 0.0209 Ω·mm²/m. The minimum area is 2 × 30 × 10.5 × 0.0209 ÷ 6 = about 2.2 mm², so the next standard size up, 4 mm², would be chosen. Always follow AS/NZS 5033 and use a licensed installer for real systems.

How to Calculate Solar DC String Cable Sizing & Voltage Drop Calculator (Step-by-Step)
  1. Enter Module Short-Circuit Current Isc (A) (A): Input your target parameter value.
  2. Enter String Open-Circuit Voltage Voc (V) (V): Input your target parameter value.
  3. Enter One-Way Cable Run (m) (m): Input your target parameter value.
  4. Enter Allowable Voltage Drop (%) (%): Input your target parameter value.
  5. Enter Rooftop Ambient Temperature (°C) (°C): Input your target parameter value.
  6. Apply Formula: Calculate using Vdrop = 2 × L × I × ρ / A | A_min = 2 × L × I × ρ / (Vdrop_allowable).
  7. Review Results: View exact computed answers, metrics, and worked mathematical proofs.
Free Publisher & Webmaster Asset

Need this calculator for your blog, publication, or client portal?

Get pre-formatted embed codes, Markdown citations for forums (Reddit/Whirlpool), or HTML anchor tags free.

Cite this Calculator

Are you using our calculation results for a university assignment, research paper, or academic report? Use the auto-generated citations below to accurately reference this tool in your bibliography.

APA 7th Edition

MyCalculator.com.au. (2026). Solar DC String Cable Sizing & Voltage Drop Calculator. Retrieved October 24, 2026, from https://www.mycalculator.com.au/calculators/engineering/solar-dc-cable-sizing

Harvard (Standard)

MyCalculator.com.au. (2026) 'Solar DC String Cable Sizing & Voltage Drop Calculator'. Available at: https://www.mycalculator.com.au/calculators/engineering/solar-dc-cable-sizing (Accessed: 24 October 2026).

Frequently Asked Questions (FAQs)

What voltage drop is allowed on a solar DC string?

AS/NZS 5033 recommends a maximum 3% drop on the DC side, but most designers target 1% to 1.5% because the lost energy compounds across every hour of generation for the system's life.

Why derate cable for rooftop temperature?

Cable current ratings are published at 30 °C ambient. A roof cavity can reach 70 °C, which can cut usable current capacity by roughly 40% and requires a larger conductor.

Free Embed Generator & Publisher Widget

Embed Solar DC String Cable Sizing & Voltage Drop Calculator on Your Site

Offer your readers, students, or clients interactive calculations. Fast, responsive, and 100% free with no login required.

Widget Customizer

650px

Recommended for publishers & educational portals to provide source citation.

Live Embed PreviewAspect Ratio: Responsive (100% × 650px)
Calculated via mycalculator.com.au — Free Australian Calculator Hub
Official Regulatory & Government Data Sources

Authoritative Standards & Verified Reference Citations

Independent & Verified

Calculations and mathematical logic on this page are grounded in published statutory rules, regulatory standards, and official government data published by the following bodies:

SponsoredMortgage Hub

Dedicated Australian home loans, borrowing capacity, mortgage repayments & refinance modeling.

Advertise here →